A cooling system using two-phase closed thermosyphon for telecommunication MCM: Experiment and simulation.
| dc.contributor.advisor | Lee, Y., | |
| dc.contributor.author | Rhi, Seok-Ho. | |
| dc.date.accessioned | 2009-03-25T19:58:10Z | |
| dc.date.available | 2009-03-25T19:58:10Z | |
| dc.date.created | 1996 | |
| dc.date.issued | 1996 | |
| dc.degree.level | Masters | |
| dc.degree.name | M.A.Sc. | |
| dc.description.abstract | The present study is concerned with a cooling system for multichip modules (MCM) in telecommunication systems. Due to the higher device operation speed and higher packaging density, the resulting heat flux is known to be 1 to 2 W/cm$\sp2$, which is one or two orders of magnitude higher than those of conventional systems, and beyond the capacity of high performance air cooling systems. A cooling system which can deal with a high heat flux of up to 4 W/cm$\sp2$ is the one that employs two-phase closed thermosyphons, (i.e., wickless heat pipes) and the present study presents the results of experimental and simulation study on a cooling system using two-phase closed thermosynphons for the cooling of MCM. | |
| dc.format.extent | 211 p. | |
| dc.identifier.citation | Source: Masters Abstracts International, Volume: 35-01, page: 0332. | |
| dc.identifier.isbn | 9780612115934 | |
| dc.identifier.uri | http://hdl.handle.net/10393/9855 | |
| dc.identifier.uri | http://dx.doi.org/10.20381/ruor-7997 | |
| dc.publisher | University of Ottawa (Canada) | |
| dc.subject.classification | Engineering, Electronics and Electrical. | |
| dc.title | A cooling system using two-phase closed thermosyphon for telecommunication MCM: Experiment and simulation. | |
| dc.type | Thesis |